Analog only – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual
Page 182

182
Rockwell Automation Publication 1756-UM533C-EN-P - February 2011
Appendix A Tag Definitions
Analog Only
This table describes the input tags available in the Analog Only data format.
Ch5Config
AB:1756_OF8H_ChConfig_Struct:C:0
Ch6Config
AB:1756_OF8H_ChConfig_Struct:C:0
Ch7Config
AB:1756_OF8H_ChConfig_Struct:C:0
PassthroughHandleTime
out
INT
Decimal
Seconds to keep a reply to a HART pass-through service request before discarding.
15 seconds recommended.
PassthroughFreq_14
BOOL
Decimal
Selects the policy for sending HART pass-through messages. See
Pass-through Setting, Ratio, and
PassthroughFreq_15
BOOL
Decimal
Table 66 - Configuration (AB:1756_OF8H:C:0)
Member Name
Type
Style
Description
Table 67 - Analog Only (AB:1756_OF8H_Analog:I:0)
Member Name
Type
Style
Description
ChannelFaults
(bits 9…15 unused)
INT
Binary
ChxFault
BOOL
Decimal
ChannelFaults.x, Indicates communication fault or fault condition from ChXStatus.
LoopOutputFault
BOOL
Decimal
ChannelFaults.8, This is a hardware fault where the module has detected that the power supply to the
isolated (analog) side of the board has failed (no power). It does not roll into any other bits. The
OK status indicator is set to solid red.
HARTFaults
SINT
Binary
ChxHARTFault
BOOL
Decimal
HARTFault.x
Indicates a problem with HART data from the field device on Channel x. Examples are HART not
enabled, HART device not connected, HART communication failure due to noise.
The following field device status conditions also cause this to be set: Device Malfunction,
PV Out of Limits, Loop Current Saturated, and Loop Current Fixed.
ModuleFaults
SINT
Binary
CalFault
BOOL
Decimal
ModuleFaults.1, 1756-IF8H module calibration failed.
Calibrating
BOOL
Decimal
ModuleStatus.2, Calibration in progress.
AnalogGroupFault
BOOL
Decimal
ModuleFaults.7, Indicates a fault has occurred on any channel (any of ChannelFaults).
Ch0Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch0Fault for Overrange, Underrange,
and CalFault.
Ch0HLimitAlarm
BOOL
Decimal
Ch0Status:0 The analog output signal is being limited by the Ch0Config.HighLimit value.If
Ch0Config.LimitAlarmLatch is 1, alarm is retained until explicitly reset.
Ch0LLimitAlarm
BOOL
Decimal
Ch0Status:1 The analog output signal is being limited by the Ch0Config.LowLimit value.If
Ch0Config.LimitAlarmLatch is 1, alarm is retained until explicitly reset.
Ch0RampAlarm
BOOL
Decimal
Ch0Status:2 Rate of change in Ch0Data exceeds Ch0Config.MaxRampRate. Rate of change is
determined by the change in Ch0Data divided by the RPI period. Thus if a step change in Ch0 cannot
be reached via the configured MaxRampRate within one RPI, then Ch0RampAlarm is set to 1. If
Ch0Config.RampAlarmLatch is 1, then Ch0RampAlarm remains set until explicitly reset using CIP
message even if the condition returns to normal. The CIP message can be sent via MSG instruction in
the Logix controller or from the the RSLogix 5000 Module Properties Limit dialog box.
Ch0InHold
BOOL
Decimal
Ch0Status:3 Channel holding its last output value, waiting for controller to match the value, indicating
that bumpless initialization of the control loop is complete.
Ch0CalFault
BOOL
Decimal
Ch0Status:4 Fault during calibration of channel 0.