Wire-off detection wiring diagram, Wire-off detection, Wiring diagram – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual
Page 72

72
Rockwell Automation Publication 1756-UM533C-EN-P - February 2011
Chapter 5
1756-IF16H HART Analog Input Module
Wire-off Detection
The 1756-IF16H module alerts you when a signal wire is disconnected from one
of its channels or the RTB is removed from the module if the channel is
configured for 4…20 mA range. When a wire-off condition occurs for this
module, two events occur:
• Input data for that channel changes to the scaled value corresponding to
the Underrange condition.
• A fault bit is set in the input tag (ChxxUnderrange and ChxxBrokenWire
tags are set to 1), which may indicate the presence of a wire-off condition.
Wiring Diagram
Use this information to wire the current inputs.
Figure 12 - Current Inputs
+
-
+
-
+
-
-
+ -
2 Wire HART Device
4 Wire HART Device
IN0+
IN1+
IN2+
IN3+
RTN
IN4+
IN5+
IN6+
IN7+
IN8+
IN9+
IN10+
IN11+
RTN
IN12+
IN13+
IN14+
IN15+
IN0-
IN1-
IN2-
IN3-
RTN
IN4-
IN5-
IN6-
IN7-
IN8-
IN9-
IN10-
IN11-
RTN
IN12-
IN13-
IN14-
IN15-
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
24V DC
Power
Supply
24V DC
Power
Supply
4 Wire
XMTR
2 Wire
XMTR
+
45124
Channel
Pin #
Usage
Usage
Pin #
00
2
IN00+
IN00-
1
01
4
IN01+
IN01-
3
02
6
IN02+
IN02-
5
03
8
IN03+
IN03-
7
10
RTN
RTN
9
04
12
IN04+
IN04-
11
05
14
IN05+
IN05-
13
06
16
IN06+
IN06-
15
07
18
IN07+
IN07-
17
08
20
IN08+
IN08-
19
09
22
IN09+
IN09-
21
10
24
IN10+
IN10-
23
11
26
IN11+
IN11-
25
28
RTN
RTN
27
12
30
IN12+
IN12+
29
13
32
IN13+
IN13+
31
14
34
IN14+
IN14+
33
15
36
IN15+
IN15+
35