Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual
Page 149

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011
149
Unlatch Alarms and Reconfigure Modules By Using Ladder Logic Chapter 10
The Configuration tab provides information on what module service to perform
and where to perform it. For example, you must use this dialog to unlatch high
high alarms (module service) on channel 0 of a module (where to perform
service).
You select a service type by clicking the drop-down. A list of available services
includes to unlatch high high, high, low low, low, low, ramp, and rate alarms.
The Communication tab provides information on the path of the message
instruction. For example, the slot number of a 1756-IF6I module distinguishes
exactly for which module a message is designated.
.
IMPORTANT
Click Browse to see a list of the I/O modules in the system.
You choose a path when you choose a module from the list.
You must name an I/O module during initial module configuration to
choose a path for your message instruction.