Module configuration errors, Additional fault codes - module level – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual
Page 160

160
Rockwell Automation Publication 1756-UM533C-EN-P - February 2011
Chapter 11
Module Troubleshooting
Module Configuration
Errors
The additional fault code value describes the configuration error if
“(Code 16#0009) Module Configuration Rejected: Parameter Error” is
displayed on the Connection Tab in RSLogix 5000 software.
Additional Fault Codes - Module Level
Table 51
shows error codes used by ControlLogix HART Analog modules for
module level conditions (conditions that do not occur in a specific channel).
Table 51 - 1756-IF8H, 1756-IF16H, and 1756-OF8H Module Level Error Codes
Additional Fault Codes
Description
16#0001
Configuration revision number invalid
Valid numbers are 0 or 1
16#0002
Filter value invalid
16#0003
RTS invalid
16#0004
Pass-through handle timeout
16#1001
Configuration does not match
In a multiple owner setup, with the configuration revision
number set to 1, the configurations must match
TIP
The 16# means this number is Hex display style.