beautypg.com

Alarm tab - 1756-if8h module, To c – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual

Page 103

background image

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011

103

Configure the Modules with RSLogix 5000 Software Chapter 7

Alarm Tab -
1756-IF8H Module

The following information describes how to configure the parameters on the
Alarm tab for the 1756-IF8H module. For more information, see

Process Alarms

on page 58

and

Rate Alarm on page 59

.

Table 23 - Module Filter Values

Module Filter, Hz

C.ModuleFilter

10

(1)

0

15

7

20

6

50

1

60 (default)

2

100

3

250

4

1000

(2)

5

(1) 10 Hz not supported in the 1756-IF16H module.
(2) Do not choose 1000 with HART enabled.