1756-if8h fault reporting – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual
Page 64

64
Rockwell Automation Publication 1756-UM533C-EN-P - February 2011
Chapter 4
1756-IF8H HART Analog Input Module
1756-IF8H Fault Reporting
The graphic below offers an overview of the fault reporting process for the
1756-IF8H module.
If set, any bit in the Channel Fault word also sets the
Analog Group Fault in the Module Fault word.
A channel calibration fault
sets the calibration fault in
the Module Fault word.
An underrange, overrange condition
sets appropriate Channel Fault bits.
When the module is calibrating, all
bits in the Channel Fault word are set.
Alarm bits 0…4 in the Channel Status word do not set additional
bits at any higher level. You must monitor these conditions here.
41514
Module Faults
Channel Faults
Channel Status Tags
7
Analog
GroupFault
6
2
Calibrating
1
CalFault
6, 5, 4, and 0 are not used for fault reporting
7
Ch7Fault
6
Ch6Fault
5
Ch5Fault
4
Ch4Fault
3
Ch3Fault
2
Ch2Fault
1
Ch1Fault
0
Ch0Fault
7
CalFault
6
Underrange
5
Overrange
4
RateAlarm
3
LAlarm
2
HAlarm
1
LLAlarm
0
HHAlarm
Ch0
Ch1
Ch2
Ch3
Ch4
Ch5
Ch6
Ch7
0
One set of tags for each channel
3
Updated
StatusReady