Analog only – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual
Page 165

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011
165
Tag Definitions Appendix A
Analog Only
This table describes the input tags available in the Analog Only data format.
HighSignal
REAL
Float
Upper current value for scaling to engineering units. Default is 20 mA. Must be more than LowSignal
and less than or equal to the maximum Input Range. See
Scaling to Engineering Units on page 98
for
more information.
LowEngineering
REAL
Float
Measured quantity in engineering units that results in a signal level equal to LowSignal. See
to Engineering Units on page 98
for more information.
HighEngineering
REAL
Float
Measured quantity in engineering units that results in a signal level equal to HighSignal. See
to Engineering Units on page 98
for more information.
LAlarmLimit
REAL
Float
User value sets low limit that causes the module to trigger a low alarm.
HAlarmLimit
REAL
Float
User value sets high limit that causes the module to trigger a high alarm.
LLAlarmLimit
REAL
Float
User value sets low low limit that causes the module to trigger a low low alarm.
HHAlarmLimit
REAL
Float
User value sets high high limit that causes the module to trigger a high high alarm.
AlarmDeadband
REAL
Float
User value sets the alarm deadband that stipulates the deadband range for the alarm trigger point.
See
on
for an illustration.
CalBias
REAL
Float
Sensor Offset in engineering units added to the measured signal before reporting Ch0.Data.
Ch1Config
AB:1756_IF8H_ChConfig_Struct:C:0
Ch2Config
AB:1756_IF8H_ChConfig_Struct:C:0
Ch3Config
AB:1756_IF8H_ChConfig_Struct:C:0
Ch4Config
AB:1756_IF8H_ChConfig_Struct:C:0
Ch5Config
AB:1756_IF8H_ChConfig_Struct:C:0
Ch6Config
AB:1756_IF8H_ChConfig_Struct:C:0
Ch7Config
AB:1756_IF8H_ChConfig_Struct:C:0
PassthroughHandle
Timeout
INT
Decimal
Seconds to keep a reply to a HART pass-through service request before discarding.
15 seconds recommended.
PassthroughCmdFreq_14
BOOL
Decimal
Selects the policy for sending HART pass-through messages. See
Pass-through Setting, Ratio, and
PassthroughCmdFreq_15
BOOL
Decimal
Table 58 - Configuration (AB:1756_IF8H:C:0)
Member Name
Type
Style
Description
Table 59 - Analog Only (AB:1756_IF8H_Analog:I:0)
Member Name
Type
Style
Description
ChannelFaults
(bit0…15
INT
Binary
Indicates a problem with analog data on Channel x or broken communication between the Logix
controller and the 1756-IF8H module.
Example: Set if analog signal is larger than 20 mA.
ChxFault
(Ch0…Ch7)
BOOL
Decimal
ChannelFaults.0…ChannelFaults.7
ChxBrokenWire
(Ch0…Ch7)
BOOL
Decimal
ChannelFaults.8…ChannelFaults.15
Indicates that current is not flowing through the module as expected. This might be caused by broken
wiring, RTB removal, or a powered-off field device.