Tag Definitions Appendix A
Analog and HART PV
This table describes the input tags available in the Analog and HART PV data
format.
Ch02Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch02Fault.
Ch03Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch03Fault.
Ch04Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch04Fault.
Ch05Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch05Fault.
Ch06Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch06Fault.
Ch07Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch07Fault.
Ch08Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch08Fault.
Ch09Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch09Fault.
Ch10Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch10Fault.
Ch11Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch11Fault.
Ch12Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch12Fault.
Ch13Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch13Fault.
Ch14Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch14Fault.
Ch15Status
SINT
Binary
Indicates various alarms on the analog signal. Also sets Ch15Fault.
ChxxData
(Ch00…Ch15)
REAL
Float
Value of analog signal on Channel xx after conversion to engineering units.
CSTTimestamp
DINT[2]
Hex
Timestamp taken at the time the input data was sampled in terms of Coordinated System Time, which
is a 64-bit value in microseconds coordinated across the modules in the 1756 backplane.
RollingTimestamp
INT
Decimal
Timestamp taken at the time the input data was sampled in millisecond resolution.
Table 63 - Analog Only (AB:1756_IF16H_Analog:I:0)
Member Name
Type
Style
Description
Table 64 - Analog and HART PV (AB:1756_IF16H_HARTPV:I:0)
Member Name
Type
Style
Description
ChannelFaults
(bit0…15)
INT
Binary
Indicates a problem with analog data on Channel x or broken communication between the Logix
controller and the 1756-IF16H module.
Example: Set if analog signal is larger than 20 mA.
ChxxFault
(Ch0…Ch15)
BOOL
Decimal
ChannelFaults.0…ChannelFaults.15
Module Status
SINT
Binary
Calibrating
BOOL
ModuleStatus.0, Calibration in progress
UpdatedStatusReady
BOOL
ModuleStatus.1, Module has collected updated Additional Device Status from HART command 48.
This status can be retrieved by using the Read Additional Status service, 16#4C. For more
information about this service, see
Read Additional Status (Service Code = 16#4C) on page 125
ModuleFaults
(bits0…5 not used)
SINT
Binary
CalFault
BOOL
Decimal
ModuleFaults.6, 1756-IF16H Module Calibration Failed.
AnalogGroupFault
BOOL
Decimal
ModuleFaults.7, Indicates a fault has occurred on any channel (any of ChannelFaults).