Additional fault codes - channel level – Rockwell Automation 1756-OF8H ControlLogix HART Analog I/O Modules User Manual
Page 161

Rockwell Automation Publication 1756-UM533C-EN-P - February 2011
161
Module Troubleshooting Chapter 11
Additional Fault Codes - Channel Level
Each module has channel level error codes that are specific to the individual
modules. These channel level error codes, which display in the Module Fault box
on the Connection tab dialog box, are described in the following tables.
Table 52 - 1756-IF8H Channel Level Error Codes
Channel x Extended Status = Channel 0 Error Value + (x *16)
Channel
Channel Status
0
1
2
3
4
5
6
7
Additional Fault
Code
s
16#0005
16#0015
16#0025
16#0035
16#0045
16#0055
16#0065
16#0075
Process Alarm Latch Set and
Disable All Alarms Set
16#0006
16#0016
16#0026
16#0036
16#0046
16#0056
16#0066
16#0076
Rate Alarm Latch Set and Alarm Disable Set
16#0007
16#0017
16#0027
16#0037
16#0047
16#0057
16#0067
16#0077
Invalid Input Range
16#0008
16#0018
16#0028
16#0038
16#0048
16#0058
16#0068
16#0078
Invalid Digital Filter
16#0009
16#0019
16#0029
16#0039
16#0049
16#0059
16#0069
16#0079
Invalid Rate Alarm
16#000A
16#001A
16#002A
16#003A
16#004A
16#005A
16#006A
16#007A
High Signal and/or Low Signal outside of
selected input range
16#000B
16#001B
16#002B
16#003B
16#004B
16#005B
16#006B
16#007B
High Signal
≤ Low Signal
16#000C
16#001C
16#002C
16#003C
16#004C
16#005C
16#006C
16#007C
Sensor Offset set to NaN
16#000D
16#001D
16#002D
16#003D
16#004D
16#005D
16#006D
16#007D
High Engineering = Low Engineering
16#000E
16#001E
16#002E
16#003E
16#004E
16#005E
16#006E
16#007E
Invalid HART rate, HART rate fixed at 1:1
16#000F
16#001F
16#002F
16#003F
16#004F
16#005F
16#006F
16#007F
High Alarm < Low Alarm
16#0010
16#0020
16#0030
16#0040
16#0050
16#0060
16#0070
16#0080
Low Low Alarm > Low
16#0011
16#0021
16#0031
16#0041
16#0051
16#0061
16#0071
16#0081
High High alarm < High Alarm
16#0012
16#0022
16#0032
16#0042
16#0052
16#0062
16#0072
16#0082
Invalid Alarm Deadband