5-22 Configuration and Programming

Example 3

When going from Run to Program mode, if both of the appropriate
bits in the Device Reset and Remote Output Reset words are reset to 0
before leaving Run mode, the RIO link device is instructed to decide
whether to hold its last output state or to reset its outputs.

To this mode

Run

Test

Program

From t

h

is m

ode

Power-up

DR = 0

ROR = 1

Default values are set automatically.
Outputs reflect those of the canner
output image.

DR = X

ROR = X

Run

ROR = X

DR = 0 Outputs are unchanged.

DR = 1 Outputs are turned off.

DR = 0 In this instance, the last ROR =
0 state switch setting is valid.

DR = 0 In this instance, ROR = 0 state
switch setting is valid.

DR = X

ROR = 1 These two combinations
reset device outputs.

DR = 1

ROR = X

DR = X

ROR = 1 These two combinations
reset device outputs.

DR = 1

ROR = X

Test

DR = 0

ROR = 1 Default values are set
automatically.

Outputs reflect those of the scanner
output image.

DR = 0 In this instance, the last ROR =
0 state switch setting is valid.

Once these outputs are reset, they
remain reset regardless of the DR and
ROR settings.

DR = X

ROR = 1 These two combinations
reset device outputs.

SR = 1

ROR = X

Outputs remain unchanged.

Program

DR = 0

ROR = 1

Default values are set automatically.
Outputs reflect those of the scanner
output image.

DR = 0

ROR = 1

These default values are set
automatically. Outputs are reset,
unless ROR is changed to 0 on the first
scan.

DR = X

ROR = X