Rockwell Automation 1747-BSN Backup Scanner Module User Manual
Page 29
![background image](/manuals/579353/29/background.png)
Publication 1747-UM010B-EN-P - September 2003
Overview 1-15
Summary for Placing Modules Used In Complementary I/O
Discrete Modules
Block Transfer Modules
The following example illustrates how I/O modules requiring two
words of the input or output image can leave unused image space.
Addressing
Method
Types of Modules
used
Placement
2-slot
8-point
Install input modules opposite output modules,
and output modules opposite input modules.
(1)
(1) If an input module resides in either slot, associated with a logical group, of the primary chassis, an input
module cannot reside in that logical group’s complimentary chassis.
1-slot
8-point, 16-point
Install input modules opposite output modules,
and output modules opposite input modules.
1/2-slot
8-point, 16-point,
32-point
Install input modules opposite output modules,
and output modules opposite input modules.
Addressing
Method
Placement
2-slot
The right slot of the primary I/O group can be another block transfer
module, or an 8-point input or output module.
The left slot of the complementary I/O group must be empty.
In the right slot of the complementary I/O group, you can place an
8-point output module; this slot must be empty if the corresponding
slot in the primary I/O group is a block transfer module.
1-slot
Leave the corresponding I/O group in the complementary chassis
empty.
1/2-slot
Leave the corresponding I/O group in the complementary chassis
empty.