beautypg.com

Procedures, Procedures -2 – Rockwell Automation 1747-BSN Backup Scanner Module User Manual

Page 40

background image

Publication 1747-UM010B-EN-P - September 2003

2-2 Quick Start for Experienced Users

Procedures

1. Ensure your chassis supports placement of the 1747-BSN

module.

Review the power requirements of your system to see that your
chassis supports placement of the scanner module. The scanner
consumes 800 mA at 5V dc.

2. Configure the module using the DIP switches. (Refer to Chapter

3, Installation and Wiring, to configure the switches.)

Set the DIP switches located on the printed circuit board.

The

six-position Configuration DIP Switch is used to select the baud
rate, configure the communication channel, and identify each
BSN module and the last BSN module.

3. Make sure system power is off; then insert the 1747-BSN scanner

module into your 1746 chassis.

In this example procedure, local slot 1 is selected.

IMPORTANT

All RIO/DH+ devices must be configured for the
same baud rate.

ATTENTION

!

Never install, remove, or wire modules with
power applied to the chassis or devices wired
to the module.

Card
Guide

Top and Bottom Module Release