beautypg.com

Rockwell Automation 1747-BSN Backup Scanner Module User Manual

Page 42

background image

Publication 1747-UM010B-EN-P - September 2003

2-4 Quick Start for Experienced Users

8. Go through the system start-up procedure.

a. Apply power.

b. Download your program to the primary and secondary SLC.

c. Place the primary SLC in Run mode.

d. Place the secondary SLC in Run mode.

The backup scanner's FAULT and ERROR LEDs are off, the RIO
LED is green, the HSSL LED is blinking and the two PRI and SEC
shows each processor Mode at this time. (This is the valid LED
pattern when in Run mode or after a Run mode to Program
mode transition.)