beautypg.com

Rockwell Automation 1747-BSN Backup Scanner Module User Manual

Page 168

background image

Publication 1747-UM010B-EN-P - September 2003

A-4 Specifications

The formula to calculate the maximum backup scanner discrete I/O
throughput without BTs present is:

T

dm-nbt

= 2T

ps +

2T

RIO +

T

adp +

T

SNo +

T

SNi +

T

id +

T

od

T

dm-nbt

=

The maximum discrete throughput without BTs in

milliseconds (ms)

To calculate T

dm-nbt

throughput, substitute values for the variables in

the formula above. Locate these values in the following documents:

Variable

Variable Description

Location of Variable

T

ps

The total processor scan time (ms)

Measured or estimated

T

RIO

The total RIO scan time (ms)

See the section RIO Scan Time
Calculation
(T

RIO

)

on page A-5.

T

adp

The adapter throughput delay. For a
1747-ASB, this is two ASB
backplane scan times.

adapter user manual

T

SNo

The backup scanner module output
delay time (ms)

See the section Backup Scanner
Output Delay Time
(T

SNo

) on page

A-14.

T

SNi

The backup scanner module input
delay time (ms)

5 ms (constant value for all formulas
in this appendix)

T

id

The input module delay time (ms)

I/O product data and I/O instruction
sheets

T

od

The output module delay time (ms)

I/O product data and I/O instruction
sheets