8-8 Switchover Considerations

disconnected from the link and the remote adapters have completed
their response to the last poll from the primary scanner.

In addition, in the event of an HSSL break, the carrier-detect circuit
prevents the secondary system from taking control of the link along
with the primary system. The figure below shows the block diagram
of the remote I/O switch.

1747-BSN

HSSL link to
primary
1747-BSN

Remote I/O
link

Smart-switch interface

Secondary processor
I/O scanner/adaptor

Carrier-detect circuit

Copy of remote I/O
data including
block transfers