A-6 Specifications

1. Use the throughput formula to calculate the maximum

throughput.

T

dm-nbt

= 2T

ps +

2T

RIO +

T

adp +

T

SNo +

T

SNi +

T

id +

T

od

T

ps

= 25.0 ms

T

RIO

= The total RIO scan time (ms)

T

SNo

= See value in the table on page B-13, T

SNo

without M0 File

Writes (Normal Mode).

T

SNi

=

5.0 ms

T

id

=

10.0 ms, which is from I/O module instruction sheets

T

od

= 1.0 ms, which is from I/O module instruction sheets

T

dm-nbt

= 2(25.0)

+

2T

RIO

+ 8.0 +

T

SNo

+ 5.0 + 10.0 + 1.0

2. Calculate the total RIO scan time (T

RIO

)

.

Locate the baud rate

(115.2K) and adapter size, which is found in the table on page
B-4. Multiply the RIO scan times listed under the 115.2K
heading by the number of each different type of rack that you
have. Add those numbers together:

T

RIO

= T

adapter 1 +

T

adapter 2 +

T

adapter 3

T

RIO

= 1(4.0 ms) + 2(5.5 ms) + 3(3.5 ms)

T

RIO

=

25.5 ms

3. Find T

SNo

on page B-13 in the table T

SNo

without M0 File Writes

(Normal Mode). For this example T

upd

> T

hold

, and there are 4

logical racks configured. Therefore:

T

SNo

= 7.0 ms

4. Substitute all the values for variables in the throughput formula

and solve for throughput:

T

dm-nbt

=

2T

ps +

2T

RIO +

2T

bp +

T

SNo +

T

SNi +

T

id +

T

od

T

dm-nbt

= 2(25.0)+ 2(25.5) + 8.0 + 7.0 + 5.0 + 10.0 + 1.0

T

dm-nbt

= 132.0 ms = maximum throughput