Rockwell Automation 1747-BSN Backup Scanner Module User Manual
Page 152
![background image](/manuals/579353/152/background.png)
Publication 1747-UM010B-EN-P - September 2003
9-10 Programming Techniques
0011
B3:5
5
B3:6
5
COP
Copy File
Source #N14:128
Dest
#M0:1.4140
Length
128
COP
L
B3:7
5
0012
B3:6
5
U
B3:7
5
0013
B3:5
6
B3:6
6
COP
Copy File
Source
#N15:0
Dest #M0:1.4268
Length
128
COP
L
B3:7
6
0014
B3:6
6
U
B3:7
6
0015
B3:5
7
B3:6
7
COP
Copy File
Source #N15:128
Dest
#M0:1.4396
Length
128
COP
L
B3:7
7
0016
B3:6
7
U
B3:7
7
Virtual DTSW Bit
for Data Block #6
Virtual DTCW Bit for Data Block #6
Virtual DTHW Bit
for Data Block #6
Virtual DTHW Bit for Data Block #6
This rung monitors the DTCW and DTSW bits for Data Block #6. When a transfer of data using Data Block #6 is not in progress, copy up
to 128 words to the appropriate M-file location for Data Block #6 in the 1747-BSN module.
Unlatch the virtual DTCW bit for Data Block #6 when the comparable virtual DTSW bit is set by the 1747-BSN module to indicate that it has
received the last data via Data Block #6. When B3:7/5 has been unlatched, the module is ready for the next data transfer via Data Block #6.
Virtual DTCW Bit for Data Block #6
Virtual DTSW Bit
for Data Block #7
Virtual DTHW Bit
for Data Block #7
This rung monitors the DTCW and DTSW bits for Data Block #7. When a transfer of data using Data Block #7 is not in
progress, copy up to 128 words to the appropriate M-file location for Data Block #7 in the 1747-BSN module.
Virtual DTCW Bit for Data Block #7
Virtual DTCW Bit for Data Block #7
Virtual DTHW Bit for Data Block #7
Unlatch the virtual DTCW bit for Data Block #7 when the comparable virtual DTSW bit is set by the 1747-BSN module to indicate that it has
received the last data via Data Block #7. When B3:7/6 has been unlatched, the module is ready for the next data transfer via Data Block #7.
Virtual DTSW Bit
for Data Block #8
Virtual DTHW Bit
for Data Block #8
This rung monitors the DTCW and DTSW bits for Data Block #8. When a transfer of data using Data Block #8 is not in progress, copy up
to 128 words to the appropriate M-file location for Data Block #8 in the 1747-BSN module.
Virtual DTCW Bit for Data Block #8
Virtual DTCW Bit for Data Block #8
Virtual DTHW Bit for Data Block #8
Unlatch the virtual DTCW bit for Data Block #8 when the comparable virtual DTSW bit is set by the 1747-BSN module to indicate that it has
received the last data via Data Block #8. When B3:7/7 has been unlatched, the module is ready for the next data transfer via Data Block #8.