Rockwell Automation 1747-BSN Backup Scanner Module User Manual
Page 146
![background image](/manuals/579353/146/background.png)
Publication 1747-UM010B-EN-P - September 2003
9-4 Programming Techniques
0004
B3:3
3
COP
Copy File
Source #M1:1.3884
Dest
#N13:128
Length
128
COP
B3:4
3
0005
B3:3
4
COP
Copy File
Source #M1:1.4012
Dest
#N14:0
Length
128
COP
B3:4
4
0006
B3:3
5
COP
Copy File
Source #M1:1.4140
Dest
#N14:128
Length
128
COP
B3:4
5
0007
B3:3
6
COP
Copy File
Source #M1:1.4268
Dest
#N15:0
Length
128
COP
B3:4
6
This rung copies the "new" Data Block #4 data from the secondary 1747-BSN to a file within the secondary processor. When the Copy is
complete, the DTHW (Data Table Handshake Word) bit for Data Block #4 (B3:4/3 = M0:1.3411/3) must be set to inform the secondary
1747-BSN that the secondary processor has received the latest Data Block and is now ready for the next block of data via Data Block #4.
This rung copies the "new" Data Block #5 data from the secondary 1747-BSN to a file within the secondary processor. When the Copy is
complete, the DTHW (Data Table Handshake Word) bit for Data Block #5 (B3:4/4 = M0:1.3411/4) must be set to inform the secondary
1747-BSN that the secondary processor has received the latest Data Block and is now ready for the next block of data via Data Block #5.
This rung copies the "new" Data Block #6 data from the secondary 1747-BSN to a file within the secondary processor. When the Copy is
complete, the DTHW (Data Table Handshake Word) bit for Data Block #6 (B3:4/5 = M0:1.3411/5) must be set to inform the secondary
1747-BSN that the secondary processor has received the latest Data Block and is now ready for the next block of data via Data Block #6.
This rung copies the "new" Data Block #7 data from the secondary 1747-BSN to a file within the secondary processor. When the Copy is
complete, the DTHW (Data Table Handshake Word) bit for Data Block #7 (B3:4/6 = M0:1.3411/6) must be set to inform the secondary
1747-BSN that the secondary processor has received the latest Data Block and is now ready for the next block of data via Data Block #7.
Virtual DTHW bit for Data Block #4
Virtual DTHW bit for Data Block #6
Virtual DTHW bit for Data Block #5
Virtual DTHW bit for Data Block #7
Virtual DTSW bit for Data Block #5
Virtual DTSW bit for Data Block #4
Virtual DTSW bit for Data Block #6
Virtual DTSW bit for Data Block #7