beautypg.com

Switch assemblies status word, Switch assemblies status word -13 – Rockwell Automation 1747-BSN Backup Scanner Module User Manual

Page 109

background image

Publication 1747-UM010B-EN-P - September 2003

Module Control and Status Word 6-13

Switch Assemblies Status
Word

The Switch Assemblies Status Word (SASW) shows the switch
assemblies configuration status for both the six-position (SW1) and the
four-position (SW2) dip switch. Bits 0 through 3 show the
four-position dip switch status, while bits 8 through 13 show the
six-position dip switch status.

Switch Assemblies Status Word

The six-position dip switch is used to configure the communication
channel and other miscellaneous information. The switches have the
following definition:

SW-1.1 and SW-1.2: Define the communication channel baud
rate as shown below.

SW-1.3: When ON means that the channel is configured as DH+.
When OFF means that the channel is configured as RIO.

SW-1.4: User identification SW. This switch can be used to
differentiate one 1747-BSN from its counterpart and identify
when a switchover occurs. This switch is user-configurable and
does not affect the operation of the module.

SW-1.5: Reserved

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

14

0

15

13 12 11 10 9

8

7

6

5

4

3

2

1

0

SW-2.1
SW-2.2
SW-2.3
SW-2.4

Reserved
Reserved
Reserved

Reserved
SW-1.1
SW-1.2
SW-1.3
SW-1.4
SW-1.5
SW-1.6
Reserved

Reserved

4-position dip switch
status

6-position dip switch
status

SASW (M1:s.3402)

SW-1.1

SW-1.2

Baud Rate (KBaud)

1

1

57.6

1

0

115.2

0

1

230.4

0

0

Disabled