Publication 1747-UM010B-EN-P - September 2003

M0-M1 Files and G Files B-5

SLC 5/02 Processor Example

If you are using a SLC 5/02 Series B processor, add 1930 µs to the
program scan time for each bit instruction addressed to an M0 or M1
data file. If you are using a SLC 5/03 Series C processor, add 1160 µs.

If you are using a SLC 5/02 Series B processor, add 1580 µs plus
670 µs per word of data addressed to the M0 or M1 file. As shown
above, 34 words are copied from #B3:0 to M0:1.0. Therefore, this
adds 24360 µs to the scan time of the COP instruction. If you are
using a SLC 5/02 Series C processor, add 950 µs plus 400 µs per word.
This adds 14550 µs to the scan time of the COP instruction.

SLC 5/04
SLC 5/05

XIC or XIO

743 µs

OTU, OTE, or
OTL

879 µs

COP to M file

735 µs plus 23 µs per word

COP from M file

722 µs plus 22 µs per word

FLL

716 µs plus 30 µs per word

MVM to M file

850 µs

any source or
Destination
M file address

694 µs

(1) Except the OSR instruction and the instruction parameters noted on page B-2.

Processor

Instruction
Type

Access Time
per Bit
Instruction or
Word of Data

Access Time per
Multi-Word Instruction

M0:2.1

1

M1:3.1

1

M0:2.1

10

COP

Copy File
Source

#B3:0

Dest

#M0:1.0

Length

34

COP