Overview 1-17
Application Considerations
If you configure a complementary device to use more I/O image
space than an associated primary device, then block transfers can only
be performed to locations in the complementary device that have
associated I/O image space in the primary device. For example, if a
primary device is 1/2 logical rack and a complementary device is a full
logical rack, block transfers can be performed only in the first 1/2
logical rack of the complementary device. Attempting block transfers
in the last half of the complementary device results in a BT error
(error 11 - device not configured).
Complementary 1771 I/O Module Details
Use the following modules in either primary or complementary I/O
chassis opposite any type of module:
•
Communication Adapter Module (1771-KA2)
•
Communication Controller Module (1771-KE)
•
PLC-2 Family/RS-232-C Interface Module (1771-KG)
•
Fiber Optics Converter Module (1771-AF)
•
DH/DH+ Communication Adapter Module (1785-KA)
•
DH+/RS-232C Communications Interface Module (1785-KE)
Use the following modules in either primary or complementary I/O
chassis opposite any type of module. However, these modules do not
work as standalone modules; each one has an associated master
module. Use care when placing the master modules in the I/O chassis:
•
Analog Input Expander Module (1771-E1, -E2, -E3)
•
Analog Output Expander Module (1771-E4)
•
Servo (Encoder Feedback) Expander Module (1771-ES)
•
Pulse Output Expander Module (1771-OJ)
1/2 logical rack
configured, but not
usable for BT since
Words 4 to 7 are not
configured for the
primary device.
Logical
Rack 8
Logical
Rack 0
1/2 logical rack
configured and usable
1/2 logical rack
configured and
usable
1/2 logical rack not
configured
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Word 0
Word1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7