Module status word, Module status word -4 – Rockwell Automation 1747-BSN Backup Scanner Module User Manual

Page 100

background image

Publication 1747-UM010B-EN-P - September 2003

6-4 Module Control and Status Word

Module Status Word

The Module Status Word (MSW) shows the status of the 1747-BSN
module itself and its counterpart in the remote system. Bits 0 through
7 show the local status while bits 8 through 15 show the remote
status. The module status bits have the following meaning:

HSSL High-Speed Serial Link status: This bit is set when the
HSSL is faulted or has communication errors in the local
1747-BSN module (bit 0) or in the remote one (bit 8). The
normal state of this bit is OFF.

LSL Local Status Link status: This bit is set when the Local
Status Link is not working well in the local system (bit 1) or
remote system (bit 9). If the system has only one 1747-BSN
module in each chassis, then the LSL is not used and this bit is
reset. The normal state of this bit is OFF.

Buffer Full: This bit is set when the secondary 1747-BSN is
receiving a second block of data before the reading of the first
block by the secondary SLC 5/0x. It could be occurring in the
local system (bit 2) or remote system (bit 10).

DH+ Communication: This bit is set when a problem occurs
with the DH+ network in the local (bit 3) or remote (bit 11)
1747-BSN module. The type of problem that may occur is
different for primary and secondary systems (as shown below).
The normal state of this bit is OFF):

1. Primary mode: The network is down or the channel is seeing

communication errors.

2. Secondary mode: Communication errors to the secondary

SLC 5/04.

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

14

0

15

13 12 11 10 9

8

7

6

5

4

3

2

1

0

HSSL
LSL

DH+ Communication
RIO Communication
Processor Fault
Primary/Secondary System
Reserved

HSSL

LSL
Buffer Full
DH+ Communication

Buffer Full

LOCAL MODULE BITS

REMOTE MODULE BITS

RIO Communication
Processor Fault

Primary/Secondary System

Reserved

MSW