M0 file - rio device reset control, Example of device inhibit control -18, M0 file - rio device reset control -18 – Rockwell Automation 1747-BSN Backup Scanner Module User Manual
Page 80: Example of device inhibit control

Publication 1747-UM010B-EN-P - September 2003
5-18 Configuration and Programming
Example of Device Inhibit Control
The 1747-BSN Scanner inhibits (sets to 1) the bits in M0:e.8 through
M0:e.11 (by default) wherever there are no configured devices
present. The illustration below compares the configured devices
(G file word 2) to the groups that the scanner automatically inhibits.
M0 File - RIO Device Reset
Control
M0 Words 16 through 19 – you use these words to command a reset
(0) of RIO device outputs when the SLC processor is in Run or Test
mode. This allows you to selectively reset logical device outputs
based on a previous condition(s) that you defined. Bits 0 to 3
correspond to the logical I/O group locations within logical racks 0, 1,
2, and 3.
To command an RIO device to a reset (0) condition (from Run or Test
mode), set the bit corresponding to the starting logical address of the
device to 1. Setting bits that do not correspond to a device starting
address does not force a reset. To remove the reset condition, reset
the bit (corresponding to the device logical starting address) to 0.
Refer to the mode table below.
Default: The SLC processor resets all bits in this field to 0 when it
enters Run or Test mode.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
1
0
x
x
x
x
x
x
x
x
x
x
x
x
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
1
0
0
1
x
x
x
x
x
x
x
x
x
x
x
x
1
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
0
2
4
6
0
2
4
6
0
2
4
6
0
2
4
6
1
0
0
1
1
1
1
1
0
1
1
0
0
1
1
1
MO (Control) File
e = slot number of the SLC rack containing the scanner x = not used/defined
Logical Rack 0 Device Inhibit Word 8
Logical Rack 1Device Inhibit Word 9
Logical Rack 2 Device Inhibit Word 10
Logical Rack 3 Device Inhibit Word 11
M0 File
M0:e.8
M0:e.9
M0:e.10
M0:e.11
Bit Number (decimal)
G File
Device Address, Word 1
RIO Logical Rack 3
Starting Group
RIO Logical Rack 2
Starting Group
RIO Logical Rack 1
Starting Group
RIO Logical Rack 0
Starting Group
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
0
2
4
6
MO (Control) File Words 16 through 19
e = slot number of the SLC rack containing the scanner
x = bit not used/ defined
Logical Rack 0 Device Inhibit Word 16
Logical Rack 1Device Inhibit Word 17
Logical Rack 2 Device Inhibit Word 18
Logical Rack 3 Device Inhibit Word 19
M0 File
M0:e.16
M0:e.17
M0:e.18
M0:e.19
Not Defined
Starting Group