Installation and Wiring 3-3

Configuration Selection

The six-position Configuration DIP Switch is used to select the baud
rate, configure the communication channel, and identify each
individual BSN module and the last BSN module. The tables below
define the DIP switch configuration settings.

Baud Rate Settings

Module Address Switch

The four-position Module Address DIP switch configures the BSN
address in the LSL. The table below shows the address that
corresponds to each setting.

DIP Switch

Position

Definition

Setting

1 and 2

Set the communication channel baud rate.

See the table on
page 2

3

Channel configuration.

DH+ = ON
RIO = OFF

4

User Identification Switch. This switch can be used
to diferentiate one 1747-BSN from its counterpart
and identify when a switchover occurs. This switch
is user-configurable and does not affect the
operation of the module.

User selectable

5

Reserved.

6

Identifies the last module in the local status link.

Last module = ON
All others = OFF

Position 1

Position 2

Baud Rate

ON

ON

57.6K

ON

OFF

115.2K

OFF

ON

230.4K

OFF

OFF

Disabled

Switch Position

(1)

(1) Switch position 4 is not used.

1747-BSN Address

1

2

3

OFF

OFF

OFF

1

ON

OFF

OFF

2

OFF

ON

OFF

3

ON

ON

OFF

4

OFF

OFF

ON

5

ON

OFF

ON

6

OFF

ON

ON

7

ON

ON

ON

8