occurs because the Restore Defaults process takes several minutes to
complete. During that time, your web browser will not be available.
[Reset Security] resets the module security back to Native mode and sets the
piadmin user password to blank. From the keyboard, press [Alt] R.
[Shutdown] shuts down the module for removal. From the keyboard, press
[Alt] U.
Keep in mind that the FactoryTalk Historian ME shutdown will take a few
minutes. Before you perform any additional operations on the Configuration
tab, please wait until the shutdown has completed.
[Startup] restarts module operations after a shutdown. From the keyboard,
press [Alt] A.
The message, Requested message timed out, will display if
RSLogix 5000 loses communication with the module at boot time. Click [OK]
and retry if you receive this message.
Normally, when Running, the Running bit in AOP Input Data value equals 1 and when
Shutdown, it equals 0. However, if the FactoryTalk Historian ME module is running in
safe mode, the Running bit toggles between 1 and 0.