Page 110

F
ACTORY
T
ALK
H
ISTORIAN
ME M
ODULE
U
SER
’
S
G
UIDE
100
Log Threshold Configuration
The Log Threshold Configuration section allows you to specify a warning level for
log files. The range is 95-99%, and the default is 95%.
When the log storage reaches its configured threshold, the FactoryTalk Historian ME
deletes older log files and logs a message in the System Log page:
“
full
.”
Archive Disk Threshold Configuration
The Archive Disk Threshold Configuration section allows you to specify a warning
level for archive disk usage. The range is 95-99%, and the default is 95%.
When the archive disk reaches its configured threshold, FactoryTalk Historian ME
stops Data Collection and logs a message in the System Log page:
“Stopping Data Collection because one or more partitions is full.”
It also deletes pimesslogfile located under /mnt/appdata/dat and logs a message in the
System Log page:
“
full.
”
Stopping Data Collection allows the module to process events from transient event
files to archive storage and make more storage space available.