In the sample scenario described in this chapter, a 2500 tag license has been assigned
against the FTMS point source in the FactoryTalk Administration Console for the
FactoryTalk Historian SE server.
1. Log into the in FactoryTalk Historian ME web interface as a FactoryTalk Security
user with Administrator privileges.
2. Click Configure Historian, and then click Data Transfer in the left navigation
bar of the web interface.
3. Enter the host name or IP address of the FactoryTalk Historian SE server in the
Host Server field. Rockwell suggests you use the host name.
4. Click [Test Connection].
5. Click [Save].
Values appear in the following fields:
FTHSE Licensed Points - the maximum number of points that have been
assigned within that FactoryTalk Historian SE server for FactoryTalk
Historian ME points. The values displayed here are read from the FactoryTalk
Historian SE server.
“FTMS” Points Available - the number of remaining licensed points that can
still be configured for Data Transfer. FTMS means FactoryTalk Historian
M
E-to-FactoryTalk Historian SE.
For example, when a 2500 tag license has been assigned in the FactoryTalk
Historian SE server and 1001 points are used against that license, 1499 points
remain to be configured for transfer. These 1499 points are available FTMS
points.
6. Make sure Auto Transfer is enabled. This feature is enabled by default.
Auto Transfer allows any point configured for Data Collection to be transferred
automatically to the FactoryTalk Historian SE server.