Configuring the Module in RSLogix 5000
This section assumes that:
The project file that contains the controller programming and configuration
information (also called the .ACD file) already exists in RSLogix 5000.
Communication devices have already been added to the I/O Configuration folder.
Logic, tags, and communication path are defined
The processor is in Remote Run mode.
To configure the module in RSLogix 5000:
1. Launch RSLogix 5000 by going to Start > Programs > Rockwell Software >
RSLogix 5000 Enterprise Series> RSLogix 5000. You can also double-click on
an .ACD file to launch RSLogix 5000.
2. Open the RSLogix 5000 project file. Select File > Open.
3. Right-click on the I/O Configuration folder and select New Module.
4. Under Specialty, select the module. You may select either the 1G or the 2G
module, depending on your installation.
5. Click [OK] and the module property sheet will open allowing you to configure the
module.