The exception algorithm relies on the following parameters:

ExcMax

Sets a limit on how long the Data Collection service can go

without reporting a value to the FactoryTalk Historian ME

server. After the ExcMax time period, the Data Collection

service sends the next new value to the FactoryTalk Historian

ME server, regardless of whether the new value is different from

the last reported value.
Note that the time between exception reports might be greater

than the exception maximum time if no new values are received

by the Data Collection service for a point. Neither the

FactoryTalk Historian ME server nor the Data Collection service

will 'create' data.

ExcMin

Sets a limit on how frequently the Data Collection service can

report values. For example, if you want the Data Collection

service to wait a full ten minutes before reporting a new value to

the FactoryTalk Historian ME server, then you would set the

ExcMin attribute to ten minutes.

Parameter

Description

Exception

Maximum

The maximum time span between exceptions, expressed in

seconds. This value is configured for each point in the ExcMax

attribute.

Exception

Minimum

The minimum time span between exceptions, expressed in

seconds. This value is configured for each point in the ExcMin

attribute.

ExcDev
(also called
Exception
Deviation

)

The deadband when exceeded causes an exception. This is

configured for each point in either the ExcDev or

ExcDevPercent attribute.

OldEvent

The value/status/timestamp of last event sent to the Snapshot.

This is the last event that passed exception report.

PrevEvent

The value/status/timestamp of last event compared to determine

whether or not to send to the Snapshot.

Field

Description