Flyingsaw, Appendix – Lenze EVS93xx FlyingSaw User Manual
Page 140
FlyingSaw
Appendix
Prepared Solution Servo PLC / ECSxA 1.1 EN
11-18
Error
number
Error code
Cause
Remedy
216
Floatfehler
Task6 Id7
217
Floatfehler
Task7 Id8
218
Floatfehler
Task8 Id9
219
Overrun
PLC_PRG Id0
The cyclic task is taking too long or
cannot be completed.
Check your program code for infinite loops
(REPEAT/UNTIL, WHILE, FOR loops) and recursive
calls and remove these structures.
220
NoCredits
The target system does not support the
technology libraries contained in the
project (e.g. positioning technology,
electronic cam).
Check code C2115/000: if no technology units are
displayed here, contact your Lenze sales representative
or the Lenze service hotline (+49) 5154 82-1111.
230
NoPrg
There is no PLC program saved in the
target system for execution.
Transfer suitable PLC program to the target system
using DDS (PRO file) or GDLoader (BIN file).
231
Unallowed Lib
The target system does not support a
library used in the source project.
Use the library for the target system.
Ensure the target system version supports the version of
the libraries used.
232
NoCamData
Motion profiles (Cam data) not available
Check the data in the Cam file
Reduce the CAN telegrams sent using the function block
L_CanPdoTransmit
−
Increase the interval time for the task
−
Select time-controlled instead of event-controlled
transmission using the byTransmitMode
−
Increase the transmission cycle on the input
tRepeatTime
.
240
TxBuffer
Overflow
On the usage of the library
LenzeCanDrv.lib
too many CAN
telegrams are sent. The transmit data
memory is full.
Increase the transmission rate on the system bus using
the code C0351/000.
241
RxBuffer
Overflow
On the use of the library
LenzeCanDrv.lib
too many CAN
telegrams are being received and cannot
be processed that quickly in the PLC
program. The receive data memory is
full.
Reduce the number of telegrams received to the free
CAN objects that are further processed by function
blocks of type L_CanPdoReceive.
Call sub-routines in which received, free CAN telegrams
are further processed at shorter interval times.
250
NoApplFlash
The data memory for additional
data/application data is missing
Replace the actual target system with a suitable target
system that contains the memory module for
additional/application data.
Contact your Lenze sales representative or the Lenze
service hotline (+49) 5154 82-1111.
251
ChckErr
(ApplRAM)
The checksum for the application data in
the RAM does not match the reference
checksum.
Contact your Lenze sales representative or the Lenze
service hotline (+49) 5154 82-1111.
Check the data connection:
−
Check the bus connectors and terminating
resistors for correct seating and correct polarity.
−
Check the parameters set for the transmission path
for freedom from ambiguity (e.g. several CAN
nodes with same bus address, baud rate, bus load
too high).
−
If necessary remove nodes from the system bus to
reduce the bus load.
252
DwnldErr
(ApplFlash)
During the transfer of the application
data to the non-volatile application data
memory an error occurred.
The source file for the additional data is corrupt
(impermissible change): re-generate the source data
(e.g. LC9 file with profile data) and repeat the transfer.
260
LifeGd
Event
The checksum for the application data in
the flash EPROM does not match the
reference checksum.
Contact your Lenze sales representative or the Lenze
service hotline (+49) 5154 82-1111.