Configuration, Change of the terminal assignment – Lenze EVS9332xS User Manual
Page 50

Configuration
Change of the terminal assignment
2.4.1
Freely assignable digital inputs
2−38
l
EDSVS9332S−EXT EN 2.0
Example:
Menu "Terminal I/O; DIGIN" (terminal I/O; digital inputs)
Here are the most important aims for digital inputs
Valid for the basic configuration C0005 = 1000.
Code
controlled by
Note
CFG
Subcode
Signal name
Signal (interface)
Selection list 2
C0885
000
R/L/Q−R
DIGIN1
(Term. X5/E1)
0051
HIGH = do not invert main setpoint (CW rotation)
C0886
000
R/L/Q−L
DIGIN2
(Term. X5/E2)
0052
HIGH = Invert main setpoint (CCW rotation)
C0787
001
NSET−JOG*1
DIGIN3
(Term. X5/E3)
0053
HIGH = Main setpoint is substituted by the fixed speed from
C0039/x
The signals are binary coded.
002
NSET−JOG*2
FIXED0
−
1000
003
NSET−JOG*4
FIXED0
−
1000
004
NSET−JOG*8
FIXED0
−
1000
C0788
001
NSET−TI*1
FIXED0
−
1000
Additional acceleration and deceleration times from C0101/x
and C0103/x
The signals are binary coded.
002
NSET−TI*2
FIXED0
−
1000
003
NSET−TI*4
FIXED0
−
1000
004
NSET−TI*8
FIXED0
−
1000
C0880
001
DCTRL−PAR*1
FIXED0
−
1000
Parameter set selection:
The signals are binary coded.
002
DCTRL−PAR*2
FIXED0
−
1000
C0881
000
DCTRL−PAR−LOAD
FIXED0
−
1000
Signal LOW−HIGH loads selected parameter set with
DCTRL−PAR*x
C0871
000
DCTRL−TRIP−SET
DIGIN4
(Term. X5/E4)
0054
LOW = Controller sets TRIP (EEr)
C0876
−
DCTRL−TRIP−RES
DIGIN5
(Term. X5/E5)
0055
Signal LOW−HIGH = Resets active trip
C0920
000
REF−ON
FIXED0
−
1000
HIGH = Start homing
C0921
000
REF−MARK
FIXED0
−
1000
LOW−HIGH edge = Stop homing
1. Select the input of the function blocks which is to be assigned to a new source under the
configuration code CFG in the code level.
– Example:
C0787/2 (CFG/subcode) determines the source for the input "NSET−JOG*2" (signal name) in
the function block "Speed setpoint conditioning" (NSET).
2. Change to the parameter level with PRG. Select the source (signal) from the indicated list. Ask
yourself: Where does the signal for controlling this input is to come from?
– Example:
"NSET−JOG*2" is to be controlled by terminal X5/E5 (interface).
– For this, select DIGIN5 (signal) and confirm with SHIFT + PRG.
3. Change to the code level with 2 * .
4. Determine the polarity of the input terminals X5/E1 to X5/E5 (HIGH active or LOW active)
under code C0114 and subcode.
– In the code level the terminal is selected via subcode.
– Change to the parameter level using PRG and select the polarity.
– Change to the code level by 2 * PRG.
5. Repeat steps 1. to 4. until all inputs required are assigned.
6. Remove undesired connections (see chapter 3.1.3). The connection so far of the terminal
X5/E5 is not cancelled automatically. If the connection is to be cancelled:
– Select C0876 in the code level (previous target of terminal X5/E5)
– Change to the parameter level using PRG.
– Select FIXED0 (signal) and acknowledge with SHIFT+PRG.