55 cw/ccw/qsp linking (r/l/q), Cw/ccw/qsp linking (r/l/q), Function library – Lenze EVS9332xS User Manual
Page 209: Function blocks

Function library
Function blocks
3.2.55
CW/CCW/QSP linking (R/L/Q)
3−157
l
EDSVS9332S−EXT EN 2.0
3.2.55
CW/CCW/QSP linking (R/L/Q)
Purpose
The FB provides a fail−safe connection for the selection of a rotation direction and the QSP function.
C0889/2
C0889/1
R/L/Q
R/L/Q-QSP
R/L/Q-R/L
R/L/Q-R
R/L/Q-L
C0885
C0886
Fig. 3−146
CW/CCW/QSP linking (R/L/Q)
Signal
Source
Note
Name
Type
DIS
DIS format
CFG
List
Lenze
R/L/Q−R
d
C0889/1
bin
C0885
2
51
−
R/L/Q−L
d
C0889/2
bin
C0886
2
52
−
R/L/Q−QSP
d
−
−
−
−
−
−
R/L/Q−R/L
d
−
−
−
−
−
−
Function
l
After mains connection and simultaneous HIGH level at both inputs, the outputs are set as
follows:
Inputs
Outputs
R/L/Q−R
R/L/Q−L
R/L/Q−R/L
R/L/Q−QSP
1
1
0
1
l
The following truth table results if one of the inputs is set to LOW once after mains connection:
Inputs
Outputs
R/L/Q−R
R/L/Q−L
R/L/Q−R/L
R/L/Q−QSP
0
0
0
1
1
0
0
0
0
1
1
0
1
1
unchanged
unchanged
l
If both inputs are set to HIGH during operation, the values at both outputs remain unchanged.