Current controller, Additional torque setpoint, Function library – Lenze EVS9332xS User Manual
Page 156

Function library
Function blocks
3.2.39
Internal motor control (MCTRL)
3−104
l
EDSVS9332S−EXT EN 2.0
Function
l
Current controller
l
Torque limitation
l
Additional torque setpoint
l
Speed controller
l
Torque control with speed limitation
l
Speed setpoint limitation
l
Angle controller
l
Quick stop QSP
l
Field weakening
l
Switching frequency changeover
3.2.39.1
Current controller
Adapt current controller via C0075 (proportional gain) and C0076 (reset time) to the machine
connected.
)
Note!
Use C0086 to select a suitable motor from the motor selection list. In this way, the
parameters of the current controller are automatically set to the correct values.
3.2.39.2
Additional torque setpoint
The input MCTRL−M−ADD serves as torque setpoint or additional torque setpoint, depending on the
control of the input MCTRL−N/M−SWT. The additional torque setpoint can be used e.g. for friction
compensation or speed injection (dv/dt).
l
When MCTRL−N/M−SWT = LOW the speed control is active.
– MCTRL−M−ADD is added to the output of the n−controller.
– The limits defined by the torque limitations MCTRL−LO−M−LIM and MCTRL−HI−M−LIM
cannot be exceeded.
l
When MCTRL−N/M−SWT = HIGH, the torque control is active.
– MCTRL−M−ADD acts as torque setpoint
– The n−controllers have a monitoring function.
l
The torque setpoint is specified in [%] of the max. possible torque (see C0057).
– Negative values mean a torque with CCW rotation of the motor.
– Positive values mean a torque with CW rotation of the motor.