48 process controller (pctrl1), Process controller (pctrl1), Function library – Lenze EVS9332xS User Manual
Page 194: Function blocks

Function library
Function blocks
3.2.48
Process controller (PCTRL1)
3−142
l
EDSVS9332S−EXT EN 2.0
3.2.48
Process controller (PCTRL1)
Purpose
The FB is used, for instance, as a higher−level controller (dancer position controller, tension controller,
pressure controller etc.).
The control characteristic follows the ideal PID algorithm, but it can also be changed over to a PI or
P characteristic.
1
0
2
Vp
Vp2
Vp3
Vp2
Vp
+
-
C0222
soll1
soll2
C0329
C0223
C0224
PCTRL1-SET
C0808/1
PCTRL1-INACT
C0808/2
C0333
C0332
3
2
PCTRL1-OUT
C0808/4
C0337
C0809/1
PCTRL1-INFLU
C0808/3
PCTRL1-ACT
PCTRL1-I-OFF
C0809/2
3
C0803
C0800
C0801
C0804
C0805
C0802
PCTRL1-ADAPT
C0336
PCTRL1
±100%
C0222
C0325
C0222
C0325
C0326
C0327
C0328
RESET
Fig. 3−127
Process controller (PCTRL1)
Signal
Source
Note
Name
Type
DIS
DIS format
CFG
List
Lenze
PCTRL1−SET
a
C0808/1
dec [%]
C0800
1
1000
Input of the process setpoint. Possible
value range:
±200%. The time
characteristic of step−change signals can
be affected via the ramp function generator
(C0332 for the acceleration time; C0333 for
the deceleration time).
PCTRL1−ACT
a
C0808/2
dec [%]
C0801
1
1000
Actual value input; value range
±200%
PCTRL1−INFLU
a
C0808/3
dec [%]
C0802
1
1000
Evaluation or suppression of the output
signal; value range
±200%
PCTRL1−ADAPT
a
C0808/4
dec [%]
C0803
1
1000
Online change of the P gain;
value range
±200%
PCTRL1−INACT
d
C0809/1
bin
C0804
2
1000
Online deactivation of the process
controller
PCTRL1−I−OFF
d
C0809/2
bin
C0805
2
1000
Online setting of the I component to zero
PCTRL1−OUT
a
−
−
−
−
−
−
Function
Setpoint and actual value are sent to the process controller via the corresponding inputs and
processed according to the selected control algorithm (control chararacteristic).