Main setpoint path, Function library, Function blocks – Lenze EVS9332xS User Manual
Page 183: 45 speed setpoint conditioning (nset), Function, Jog setpoints, Setpoint inversion

Function library
Function blocks
3.2.45
Speed setpoint conditioning (NSET)
3−131
l
EDSVS9332S−EXT EN 2.0
Signal
Source
Note
Name
Type
DIS
DIS format
CFG
List
Lenze
NSET−N
O
C0046
dec [%]
C0780
1
50
Intended for main setpoint, other signals
are permissible
NSET−NADD
O
C0047
dec [%]
C0782
1
5650
Intended for additional setpoint, other
signals are permissible
NSET−JOG*1
d
C0799/4
bin
C0787/1
2
53
Selection and control of overriding "fixed
setpoints" for the main setpoint
NSET−JOG*2
d
C0799/5
bin
C0787/2
2
1000
NSET−JOG*4
d
C0799/6
bin
C0787/3
2
1000
NSET−JOG*8
d
C0799/7
bin
C0787/4
2
1000
NSET−TI*1
d
C0799/8
bin
C0788/1
2
1000
Selection and control of alternative
acceleration and deceleration times for the
main setpoint
NSET−TI*2
d
C0799/9
bin
C0788/2
2
1000
NSET−TI*4
d
C0799/10
bin
C0788/3
2
1000
NSET−TI*8
d
C0799/11
bin
C0788/4
2
1000
NSET−N−INV
d
C0799/1
bin
C0781
2
10251
Control of the signal inversion for the main
setpoint
NSET−NADD−INV
d
C0799/2
bin
C0783
2
1000
Control of the signal inversion for the
additional setpoint
NSET−RFG−0
d
C0799/12
bin
C0789
2
1000
The main setpoint integrator is led to zero
via the current T
i
times.
NSET−RFG−STOP
d
C0799/13
bin
C0790
2
1000
Keeping (freezing) of the main setpoint
integrator to its actual value.
NSET−CINH−VAL
O
C0798/1
dec [%]
C0784
1
5001
Here, the signal is applied which is to be
accepted by the main setpoint integrator
when the controller is inhibited
NSET−SET
O
C0798/2
dec [%]
C0785
1
5000
Here, the signal is applied which is to be
accepted by the main setpoint integrator
when the NSET−LOAD input is set
NSET−LOAD
d
C0799/3
bin
C0786
2
5001
Control of both ramp function generators in
special situations, e.g. QSP
NSET−OUT
O
−
−
−
−
−
−
NSET−RFG−I=0
d
−
−
−
−
−
−
Function
l
Main setpoint path
l
JOG setpoints
l
Setpoint inversion
l
S ramp
3.2.45.1
Main setpoint path
l
The signals in the main setpoint path are limited to the value range ±199.99 %.
l
The signal at input NSET−N is led via the function JOG selection.
l
The JOG function has priority over the setpoint input NSET−N. This means a selected JOG
value deactivates the input. The subsequent signal conditioning the JOG value instead.