Quick stop (qsp), Function library, Function blocks – Lenze EVS9332xS User Manual
Page 110: 23 control of the drive controller (dctrl), Function, Operation inhibited (disable), Controller inhibit (cinh), Trip−set, Trip−reset, Change of parameter set (par)

Function library
Function blocks
3.2.23
Control of the drive controller (DCTRL)
3−58
l
EDSVS9332S−EXT EN 2.0
Signal
Source
Note
Name
Type
DIS
DIS format
CFG
List
Lenze
DCTRL−CINH1
d
C0878/1
bin
C0870/1
2
1000
HIGH = Inhibit controller
DCTRL−CINH2
d
C0878/2
bin
C0870/2
2
1000
HIGH = Inhibit controller
DCTRL−TRIP−SET
d
C0878/3
bin
C0871
2
54
HIGH = Fault signal EEr
DCTRL−TRIP−RESET
d
C0878/4
bin
C0876
2
55
LOW−HIGH signal = TRIP reset
DCTRL−PAR*1
d
C0884/1
bin
C0880/1
2
1000
Selecting a parameter set
DCTRL−PAR*2
d
C0884/2
bin
C0880/2
2
1000
Selecting a parameter set
DCTRL−PAR−LOAD
d
C0884/3
bin
C0881
2
1000
LOW−HIGH edge = Loading a parameter set
DCTRL−QSP
d
−
−
−
−
−
HIGH = Drive performs quick stop
DCTRL−RDY
d
−
−
−
−
−
HIGH = Ready for operation
DCTRL−CINH
d
−
−
−
−
−
HIGH = Controller reset
DCTRL−IMP
d
−
−
−
−
−
HIGH = High−resistance power output
stages
DCTRL−TRIP
d
−
−
−
−
−
HIGH = Active fault
DCTRL−WARN
d
−
−
−
−
−
HIGH = Active warning
DCTRL−MESS
d
−
−
−
−
−
HIGH = Active message
DCTRL−FAIL
d
−
−
−
−
−
−
DCTRL−CW/CCW
d
−
−
−
−
−
LOW = CW rotation, HIGH = CCW rotation
DCTRL−NACT=0
d
−
−
−
−
−
HIGH = Motor speed < C0019
DCTRL−STAT*1
d
−
−
−
−
−
General status (binary coded)
DCTRL−STAT*2
d
−
−
−
−
−
General status (binary coded)
DCTRL−STAT*4
d
−
−
−
−
−
General status (binary coded)
DCTRL−STAT*8
d
−
−
−
−
−
General status (binary coded)
DCTRL−INIT
d
−
−
−
−
−
−
DCTRL−PARBUSY
d
−
−
−
−
HIGH = Parameter set changeover is active
DCTRL−PAR*1−O
d
−
−
−
−
−
Parameter set X is active (binary coded)
DCTRL−PAR*2−0
d
−
−
−
−
−
Parameter set X is active (binary coded)
Function
l
Quick stop (QSP)
l
Operation inhibited (DISABLE)
l
Controller inhibit (CINH)
l
TRIP−set
l
TRIP−RESET
l
Change of parameter set (PAR)
l
Controller state
3.2.23.1
Quick stop (QSP)
The drive is braked to standstill via the deceleration ramp C105 and generates a holding torque.
l
The function can be controlled by three inputs
– Control word CAN−CTRL bit 3 of CAN−IN1
– Control word AIF−CTRL bit 3 of AIF−IN
– Control word C0135 bit 3
l
All inputs are linked by an OR−operation.
l
C0136/1 displays the control word C0135