Electrical installation, Operation at rated power, Operation with increased rated power – Lenze EVF9333 User Manual
Page 166

Electrical installation
Standard devices in the power range 0.37 ... 11 kW
Mains connection: Fuses and cable cross−sections
l
166
EDKVF9333V DE/EN/FR 7.1
Operation at rated power
9300
Rated fuse current
Cable cross−section
FI
1)
Fuse
Circuit−breaker
Laying system L1, L2, L3, PE
B2
C
Type
[A]
[A]
[mm
2
]
[mm
2
]
[mA]
Operation without mains choke/mains filter
EVF9321−xV
6
C6, B6
2)
1
1
300
EVF9322−xV
6
C6, B6
2)
1
1
EVF9323−xV
10
B10
1.5
1
EVF9325−xV
25
B20
4
2.5
Operation with mains choke/mains filter
EVF9321−xV
6
C6, B6
2)
1
1
300
EVF9322−xV
6
C6, B6
2)
1
1
EVF9323−xV
10
B10
1.5
1
EVF9324−xV
10
B10
1.5
1
EVF9325−xV
20
B16
2.5
2.5
EVF9326−xV
32
B25
˘
4
1)
Universal current−sensitive earth−leakage circuit breaker
2)
For short−time mains interruptions, use circuit breakers with tripping characteristic "C"
Operation with increased rated power
9300
Rated fuse current
Cable cross−section
FI
1)
Fuse
Circuit−breaker
Laying system L1, L2, L3, PE
B2
C
Type
[A]
[A]
[mm
2
]
[mm
2
]
[mA]
Operation with mains choke/mains filter
EVF9321−xV
6
C6, B6
2)
1
1
300
EVF9322−xV
6
C6, B6
2)
1
1
EVF9323−xV
10
B10
1.5
1
EVF9324−xV
10
B10
1.5
1
EVF9325−xV
20
B16
2.5
2.5
1)
Universal current−sensitive earth−leakage circuit breaker
2)
For short−time mains interruptions, use circuit breakers with tripping characteristic "C"