Technical data, General data and operating conditions, 3technical data – Lenze EVF9333 User Manual
Page 129

Technical data
General data and operating conditions
3
l
129
EDKVF9333V DE/EN/FR 7.1
3
Technical data
3.1
General data and operating conditions
General data
Conformity and approval
Conformity
CE
2006/95/EC
Low−Voltage Directive
2004/108/EG
EMC Directive
Approval
UL
cULus
Power Conversion Equipment (File No. E132659)
Protection of persons and equipment
Type of protection
EN 60529
IP20
IP41 in case of thermally separated installation (push−through
technique) between the control cabinet (inside) and the
environment.
NEMA 250
Protection against accidental contact in accordance with type
1
Earth leakage current
IEC/EN 61800−5−1
> 3.5 mA AC
> 10 mA DC
Observe regulations and safety
instructions!
Insulation of control
circuits
IEC/EN 61800−5−1
Safe mains isolation by double (reinforced) insulation for the
terminals X1 and X5.
Basic insulation (single isolating distance) for the terminals
X3, X4, X6, X8, X9, X10 and X11.
Insulation resistance
IEC/EN 61800−5−1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
Protective measures
Against short circuit, earth fault (earth−fault protected during
operation, limited earth−fault protection during operation),
overvoltage, motor stalling, motor overtemperature (input for
PTC or thermal contact)
EMC
Noise emission
IEC/EN 61800−3
Cable−guided, up to 10 m motor cable length with mains
filter A: category C2.
Radiation, with mains filter A and installation in control
cabinet: category C2
Interference immunity
IEC/EN 61800−3
Category C3