Mechanical installation, Dimensions, Mounting cutout in control cabinet – Lenze EVF9333 User Manual
Page 140

Mechanical installation
Standard devices in the power range 0.37 ... 11 kW
Thermally separated mounting (push−through technique)
l
140
EDKVF9333V DE/EN/FR 7.1
4.1.3
Thermally separated mounting (push−through technique)
For mounting in push−through technique, the drive controller of type EVF93xx−EV must be
used. In addition, the mounting set for push−through technique is required.
Type
Mounting set
Type
Mounting set
EVF9321−EV, EVF9322−EV
EJ0036
EVF9323−EV, EVF9324−EV
EJ0037
EVF9325−EV, EVF9326−EV
EJ0038
Dimensions
a1
a1
c1
c1
a
a
c
c
g
g
d1
d1
d1
d1
d
d
b1
b1
b
b
L
L
1
0
e
f
9300vec115
Fig. 4−2
Dimensions for thermally separated mounting 0.37 ... 11 kW
9300 vector
Dimensions [mm]
Type
a
a1
b
b1
c
c1
d
d1
e
1)
f
g
EVF9321−EV
EVF9322−EV
0
112.5
78
385.5
350
60
95.5
365.5
105.5
250
92
6.5
EVF9323−EV
EVF9324−EV
0
131.5
97
385.5
350
79
114.5
365.5
105.5
250
92
6.5
EVF9325−EV
EVF9326−EV
1
169.5
135
385.5
350
117
152.5
365.5
105.5
250
92
6.5
1)
For a fieldbus module plugged onto X1, consider mounting space for connecting cables
Mounting cutout in control cabinet
9300 vector
Dimensions [mm]
Type
Width
Height
EVF9321−EV
EVF9322−EV
0
82
350
EVF9323−EV
EVF9324−EV
0
101
350
EVF9325−EV
EVF9326−EV
1
139
350