Fold−out page on the right), Connections and interfaces, Status displays – Lenze EVF9333 User Manual
Page 110

l
110
EDKVF9333V DE/EN/FR 7.1
EVF9330 ... EVF9333
0Fig. 0Tab. 0
(fold−out page on the right)
Position
Description
0
Controller
1
Fixing bracket for standard mounting
2
EMC shield sheet with fixing screws for shielded control cables
3
Cover with fixing screws
4
Shield clamp and strain relief for the motor cable
5
Strain relief for the PE motor cable and the feed cable for the motor temperature monitoring with PTC thermistor
or thermal contact (NC contact)
Connections and interfaces
Position
Description
L1, L2, L3, PE Mains connection
^ 159
+UG, −UG
DC supply
^ 159
U, V, W, PE
Motor connection
^ 159
T1, T2
Connection of PTC thermistor or thermal contact (NC contact) of the motor
^ 159
X1
AIF interface (automation interface)
Slot for communication module (e. g. XT EMZ9371BC keypad)
−
X3
Jumper for setting analog input signal at X6/1, X6/2
^ 205
X4
System bus (CAN) connection
^ 206
X5
Connection of digital inputs and outputs
^ 199
X6
Connection of analog inputs and outputs
^ 199
X8
Connection of incremental encoder with TTL level or SinCos encoder and KTY temperature sensor
of the motor
^ 207
X9
Connection of digital frequency input signal
^ 210
X10
Connection of digital frequency output signal
X11
Connection of K
SR
relay output for "safe standstill" (for variants V004 and V024 only)
^ 202
Status displays
Position
LED red
LED green
Operating status
Off
On
Controller is enabled
On
On
Mains is switched on and automatic start is inhibited
Off
Blinking slowly
Controller is inhibited
Off
On
Motor data identification is active
Blinking quickly
Off
Undervoltage or overvoltage
Blinking slowly
Off
Active fault