8 Programming

73

8.4.3 Scaling

The scaling start/end value and the dimen-
sion (unit) are defined to record the meas-
urement. For the alpha-numerical presenta-
tion of the measurement on the display and
on the chart, the number format is selected.

Example:
A temperature transmitter supplies a voltage
within the range of 0 — 10V. This range cor-
responds to a temperature of 200 — 600°C.

Programming:
Unit: °C
Scaling start:

200

Scaling end:

600

Number format:

XXX.X

Section 7.4

Display

Edit

Selection/input

with keys

Enter

Continue with

SCALING

E

3 SCALING

Select recording channel

h

,

R

E

2

2

3 DIMENSION: _ _ _ _

5 digits freely selectable

h

,

R

,

S

E

3

3

3 ZERO
+200.0 °C

Input start of scaling

h

,

R

,

l

,

r

,

S

E

4

4

3 FULL
+600.0 °C

Input end of scaling

h

,

R

,

l

,

r

,

S

E

Check
zero

<>

full

5

5

3 DECIMAL POINT:
x.xxx

Select decimal place :
AUTO, x.xxx, xx.xx, xxx.x,
xxxx.

h

,

R

E

h

forwards

R

backwards