4 Electrical connection

17

Analogue inputs

Input 1

Input 2

Input 3

Resistance thermometer/
potentiometer in 2-wire circuit

Field

Field

Field

1.

2.

3.

*R

comp

=R

line

Resistance thermometer/
potentiometer in 3-wire circuit

Resistance thermometer/
potentiometer in 4-wire circuit

Resistance transmitter
with 3-wire connection

A = start
S = slider
E = end

Field

External relay module ER8

Communication with ex-
ternal relay module ER8

8.

Supply for external 2-wire
transmitter

24V ±5%, 45 mA

Logic operating inputs

Contact operation

LOW = R

OFF

100k

Ω

min.

HIGH = R

ON

50

Ω

max

.

Terminal 7=logic input 1
...
Terminal 14=logic input 8

Minimum pulse duration:

HIGH 500 msec
LOW 500 msec

Voltage operation

LOW = 0 — 5 V DC
(not activated)

HIGH = 20 — 35 V DC
(activated)

Terminal 7=logic input 1
...
Terminal 14=logic input 8

Serial interface
RS422 or RS485

Communication with
higher-level systems

9.