beautypg.com

JUMO 706021 LOGOLINE 500d Line Recorder Operating Manual User Manual

Page 124

background image

124

12 Appendix

Power consumption
35 VA max.

Data back-up
by lithium battery in RAM, more than 4 years;
by storage capacitor 2 days at 15 — 25 °C
ambient temperature.
Additional back-up in EEPROM.

Electrical connection
at the back through screw-clamp connec-
tors, max. conductor cross-section 2.5 mm

2

or 2 x 1.5mm

2

with core sleeves.

Setup connector behind the swing-up LED
dot-matrix display.

Permitted ambient
temperature range
–10 to +50 °C

Ambient temperature drift
0.3 % per 10°C

Permitted storage
temperature range
–20 to +70°C

Climatic conditions
rel. humidity 75 % max., no condensation

Operating position
NL 90 ± 30 to DIN 16 257 (vertical)

Protection
to EN 60 529 Category 2
- front IP54
- front IP65 (with extra code 266,

without extra code 265)

- rear IP20

Electromagnetic compatibility (EMC)
EN 61 326
Interference emission:
Class B
Immunity to interference:
industrial requirements

Electrical safety
to EN 61 010

Approvals/marks of conformity
Mark of conformity:
c UL us
Testing laboratory:
Underwriters Laboratories
Certificates/certification numbers:
E 201387
Test basis:
UL 3111-1
CAN/CSA-C22.2 No. 1010.1-92
valid for:
the flush-mounted instrument;
not in conjunction with any housing extra
code