beautypg.com

6 preparation, 1 operating modes and status, Preparation – JUMO 706021 LOGOLINE 500d Line Recorder Operating Manual User Manual

Page 20: Operating modes and status, 20 6 preparation

background image

20

6 Preparation

6.1 Operating modes and status

Operating mode/status

Description

Basic status

Basic status of the recorder with signal acquisition and
processing.
The display shows, depending on setting:

- instrument designation, date and time

- one channel and its measurement as number

or bargraph

- or status/error messages.

The display can be altered during recording, using the
keys

h

and

R

.

If there is a status/error message, it is shown flashing at
regular intervals instead of the current display.

Stop

Stop by key

Recording is stopped and continued using key

S

.

In the stop status the display flashes STOP.

Stop via external stop

External stop can be operated through a signal at a
logic input on the back of the recorder. In the external
stop status the display flashes EXTERNAL STOP.

Chart speeds

Normal chart speed

The chart is advanced at the speed programmed under
chart speed.
Section 8.2.1

Limit operation

When input goes above/below the programmed limits,
the recorder switches to the chart speed programmed
under “limit feed”.
 Section 8.4.5

Section 8.5.3

Section 10.4

External speed

On a signal applied to a logic input at the back of the
recorder, it switches to the chart speed programmed
under “feed extern”.
 Section 8.6.7

Section 10.4