n115 setting
•
Accel/decel time selection during stall prevention (n116)
With this function, acceleration/deceleration time when moving to prevent stalling
during operations can be assigned to the two parameters, n021 and n022.
n116 setting
•
Stall prevention (current limit) function during acceleration (n092)
To prevent over voltage during deceleration, the inverter automatically extends the
deceleration time according to the value of the main circuit DC voltage. When
using an optional braking resistor, set n092 to 1.
Setting
Function
0
The stall prevention level becomes the level set for the parameter n094 in all frequency areas
1
The following shows that the stall prevention level is automatically decreased in the parameter output
range (Max. frequency>Max. voltage output frequency).
The lower limit is 40% of the set value of n094.
Parameter
No.
Name
Unit
Setting Range
Initial Setting
n116
Accel/decel time selection
during stall prevention
-
0=Disabled
1=Enabled
0
Setting
Function
0
Accel/decel time is set by accel/decel time 1or 2.
1
Accel/decel time is fixed at accel/decel time 2(n021, n022)
Setting
Stall prevention (current limit) during
deceleration
0
Provided
1
Not provided (when braking resistor is mounted