Frequency reference by pulse train input – IDEX Health & Science VS-606V7 Series User Manual
Page 85
85
•
Frequency Reference by Pulse Train Input
Frequency reference can be set by pulse train input from the multi-function input
terminal.
•
Input pulse specifications
•
Low-level voltage: 0.8V or less
•
High-level voltage: 3.5 to 32V
•
Duty Cycle: 30 to 70%
•
Pulse frequency: 0 to 33 kHz
•
Frequency reference method
Frequency reference is a value obtained by multiplying the ratio of the maximum
input pulse frequency and actual input pulse frequency by the maximum output
frequency.
Parameter
No.
Name
Unit
Setting range
Initial Setting
n003
Run command selection
1
0 to 2
0
n004
Frequency reference selection
1
0 to 6
0
n149
Pulse train input scaling 1=10Hz
1
100 to 3300
(33kHz)
2500
(25kHz)
Reference freq
Input pulse frequency
Minimum pulse train frequency (n149)
10
×
-----------------------------------------------------------------------------------------------------------------
max output frequency (n011)
×
=
Run/stop and FWD/REV can
be selected by a switch
connected to the control circuit
terminal.
Frequency setting can be set
by pulse train input signal [0 to
100% (maximum frequency)/0
to 33kHz] connected to the
multi-function input terminal.