IDEX Health & Science VS-606V7 Series User Manual
Page 74
74
Initial setting
Terminal function at 3-wire sequence selection
When 0 is set at the terminal S3 (n052), terminal S1 becomes run command, terminal
S2 becomes stop command, and terminal S3 becomes FWD/REV run command.
•
LOCAL/REMOTE select (setting: 17)
Select operation reference either by the digital operator or by the settings of
operation method selection (n003) and frequency reference selection (n004).
LOCAL/REMOTE select is available only during stop.
Open:
Run according to the setting of run command selection (n003) or
frequency reference selection (n004)
Closed: Run by frequency reference and run command from the digital operator.
No.
Terminal
Initial Setting
Function
n050
S1
1
Forward run command (2-wire sequence)
n051
S2
2
Reverse run command (3-wire sequence)
n052
S3
3
External fault
n053
S4
5
Fault reset
n054
S5
6
Multi-step speed reference 1
n055
S6
7
Multi-step speed reference 2
n056
S7
10
JOG command