Motor Overload Protection

Electronic thermal overload relay

Instantaneous Overcurrent

Motor coasts to a stop at approx. 250% of inverter rated
current

Overload

Motor coasts to a stop after 1 minute at 150% of inverter
rated output current

Overvoltage

Motor coasts to a stop if DC bus voltage exceed 410V

Undervoltage

Stops when DC bus voltage is approx. 200V or less
(approx. 160V or less for single-phase series)

Momentary Power Loss

Following items are selectable: Not provided (stops if
power loss is 15ms or longer), continuous operation if
power loss is approx. 0.5s or shorter, continuous
operation

Cooling Fin Overheat

Protected by electronic circuit

Stall Prevention Level

Can be set individual level during accel/decel, provided/
not provided available during coast to a stop

Cooling Fan Fault

Protected by electronic circuit (fan lock detection)

Ground Fault

Protected by electronic circuit (overcurrent level)

Power Charge Indication

ON until the DC bus voltage becomes 50V or less. RUN
lamp stays ON or digital operator LED stays ON.

Ot

her F

unc

ti

ons

Input

S

ignal

s

Multi-function Input

Seven of the following input signals are selectable:
Forward/reverse run (3-wire sequence), fault reset,
external fault (NO/NC contact input), multi-step speed
operation, Jog command, accel/decel time select, external
baseblock (NO/NC contact input), speed search
command, accel/decel hold command, LOCAL/REMOTE
selection, communication/control circuit terminal
selection, emergency stop fault emergency stop alarm
UP/DOWN command, self test, PID control cancel, PID
integral reset/hold

O

u

tp

ut

S

ignal

s

Multi-function Output

Following output signals are selectable (1 NO/NC contact
output, 2 photo-coupler outputs): Fault, running, zero
speed, at frequency, frequency detection (output
frequency

or

set value), during over torque detection,

during undervoltage detection, minor error, during
baseblock, operation mode, inverter run ready, during
fault retry, during UV, during speed search, data output
through communication, PID feedback loss detection

Standard Functions

Voltage vector control, full-range automatic torque boost,
slip compensation, DC injection braking current/time at
start/stop frequency reference bias/gain, MEMOBUS
communications (RS-485/422, max. 19.2K bps), PID
control, energy-saving control, parameter copy, frequency
reference with built-in potentiometer
Unit selection for frequency reference setting/display

Voltage Class

200V single- / 3-phase

Model

CIMR-V7*C

‰‰‰‰

3-phase

20P1 20P2 20P4 20P7 21P5 22P2 23P7 25P5 27P5

Single-phase

B0P1 B0P2 B0P4 B0P7 B1P5 B2P2 B3P7

-

-