beautypg.com

Using energy-saving control mode, Energy-saving control selection (n139) – IDEX Health & Science VS-606V7 Series User Manual

Page 105

background image

105

Using Energy-saving Control Mode

Verify that the parameter n002 is set to 0 (V/f control mode) when performing
energy-saving control. Setting n139 to 1 enables the energy-saving control
function.

Normally it is not necessary to change the setting. However, if the motor
characteristics are different from a Yaskawa standard motor, refer to the description
below and change the parameter setting accordingly.

Energy-saving Control Mode (n140, n158)

Calculates the voltage for the best motor efficiency when operating in energy-
saving control mode. The calculated voltage becomes the output voltage reference.
The factory setting is set to the max. applicable motor capacity of a Yaskawa
standard motor.
The greater the energy-saving coefficient is, the greater the output voltage becomes.

When using a motor other than a Yaskawa standard motor, set the motor code
corresponding to the voltage and capacity to n158. Then, change the setting of the
energy-saving coefficient K2 (n140) by 5% so that the output power becomes the
smallest.

When the motor code is set to n158, the energy-saving coefficient K2, which
corresponds to the motor code, is set n140.

Setting depends on inverter capacity.

Energy-saving Control Selection (n139)

Parameters

No.

Name

Unit

Setting

Range

Initial

Setting

n139

Energy-saving

control selection

-

0: Disabled

1: Enabled

0

Parameter

No.

Name

Unit

Setting

Range

Initial

Setting

n140

Energy-saving

control coefficient K2

-

0.0 to 6550

*

n158

Motor Code

-

0 to 70

*