77

Notes:
(1) When UP/DOWN command is selected, the upper limit speed is set regardless of frequency

reference.

(2) Lower limit value is either minimum output frequency (n016) or frequency reference lower limit

(n034) (whichever is greater).

(3) When the FWD (REV) run command is input, operation starts at the lower limit speed without an

UP/DOWN command.

(4) If the jog command is input while running by the UP/DOWN command, the jog command has

priority.

(5) Multi-step speed reference 1 to 4 is not effective when UP/DOWN command is selected. Multi-

step speed reference is effective during running in hold status.

(6) When “1” is set for HOLD output frequency memory selection (n100), output frequency can be

recorded during HOLD.

Setting

Description

0

Output frequency is not recorded during HOLD.

1

When HOLD status is continued for 5 seconds or longer, the output frequency
during HOLD is recorded and the inverter restarts at the recorded frequency.

Upper limit speed = Maximum output frequency (n011)

x Frequency reference upper limit (n033)/100